
FUME HOODS
Requirement for Fume Hoods
- handling of hazardous materials (solids, liquids or gas)
- prevents exposure to fumes, vapours, dusts, and aerosols carried in air
- provides a cleanable work surface
- a temporary work surface - not a storage unit
- breathing zone - the volume of air around your nose and mouth which has the potential to be inhaled under normal circumstances
- face velocity - inward airflow from the sash in feet per minute (fpm)
- safe working sash height is variable
Fume Hood Anatomy
- sash
- by-pass grill (CAV)
- work surface
- air foil
- baffles
- access ports
- controller module
- light switch
- utility supplies
- electrical supply
- storage units
Alarms or Monitors
- never turn off or deactivate alarms or monitors
- if the alarm sounds or the monitor lights indicate low flow:
- work should be stopped, close all containers, equipment turned off, and the sash lowered
- lab personnel should leave the area if highly toxic or volatile chemicals are being used
- if there is a likelihood that airborne contaminants will be released from the fume hood into the laboratory, please immediately contact your building services
- report all problems to your supervisor immediately
- verify control panel on your unit
- read user manual
- monitor air flow alarm
- MUMC fumehoods using VentAlert system can change their battery according to these instructions.
Environmental Protection
- fume hoods exhaust 100% of the air into the environment
- no protection of the environment from hazardous fumes, vapors, aerosols and dusts
- minimize these hazardous releases by keeping containers closed at all times
- evaporation is prohibited as a method of chemical waste disposal
Sustainability
- conditioned air (heated or cooled, humidified or dehumidified) is exhausted through fume hoods
- fume hood exhaust systems run 24 hours a day, 7 days a week
- are not put in low consumption states during off hours in the building like the air handling units
- constant air volume systems are present in some buildings
- do not allow for 'emergency purge' of fume hood even if you do have a controller panel with an emergency purge button
- air consumption is not altered when the sash is closed
- airflow increased through by-pass and air foil
- variable air volume systems are present
- allows for emergency purge of fume hood via controller panel if that feature is present
- air consumption decreases when sash is closed
Specifications for Fume Hoods
- manufacturer's specifications
- user manual
- CSA Z316.5-15, "Fume hoods and associated exhaust systems"
- SEFA 1-2010, "Recommended Practices For Laboratory Fume Hoods"
- ASHRAE 110-2016, “Method of Testing Performance of Laboratory Fume Hoods"
- AEBC R-52 rev 1, "Design Guide for Basic and Intermediate Level Radioisotope Laboratories".
Preparing a Fume Hood for Work
- review the SDS for the chemicals in use, review SOPs for work to be done
- don PPE (lab coat, chemical resistant gloves, long pants, close toed shoes, eye protection)
- verify an appropriate chemical spill kit is available
- ensure you are aware of the closest emergency eyewash and shower
- turn on the light, test the alarm and verify inflow velocity on the controller panel
- verify certification is up to date by viewing sticker
- open the sash and load your equipment, samples and reagents
- work at least 6" inward from the air foil
- do not block rear baffles
- raise large objects by 3"
- lower sash to working height or close vertical panels to ensure one panel is in front of you
Working in the Fume Hood
- monitor the fume hood when performing ongoing or reactive experiments
- keep pedestrian traffic to a minimum
- avoid rapid or excessive movement in front of the fume hood
- place:
- experimental materials and equipment at least 6 inches back from the face
- large objects two to three inches above the work surface
- keep rear baffle openings clear
- keep papers, paper towels, work surface diapers, vials, and other small objects from being drawn into the fume hood’s ventilation system
Maintain Air Flow
- be aware of eddy currents inside the hood
- never cause air turbulence close to the fume hood eg exhaust from other equipment
- keep nearby doors and windows closed when working in a fume hood
- keep people traffic away from a fume hood when in use
- move slowly in the hood
- don’t open the sash rapidly
Small Chemical Spill in Fume Hood
- stop working immediately and assess for
- personal contamination (proceed to emergency flushing equipment)
- hazardous material release from fume hood
- potential for fire or explosion
- equipment damage
- air flow status
- notify laboratory occupants
- retrieve chemical spill kit
- apply absorbent materials
- apply chemical neutralizer
- collect absorbed liquids into a double poly lined bag, labelled
- complete incident reporting per RMM1000
Heat Generation
- equipment and experimental procedures can generate excessive heat
- heat causes changes in air currents
- heat causes air to expand
- negative pressure of the fume hood may be overcome leading to relase into the user's breathing zone
Over Crowded Fume Hood
- over-crowded fume hoods are a hazard
- dispose or donate excess chemicals
- move chemicals do another flammables / corrosives storage unit
- prop up large equipment on blocks to allow air flow
- most vapours flow down and accumulate at the work surface
- recommend use of fume hood shelves
Other Precautions
- do not use hot plates or heated stirrers in a fume hood when flammables or combustibles are present
- never use paper, paper towel, kimwipes or any light items which can get sucked up into the ducting
- evaporation of hazardous chemicals is prohibited as a method of disposal
- never modify a chemical fume hood
- no other types of exhaust can be connected to the fume hood exhaust system without a proper engineering assessment by Facilities Services or your hospital host engineering department
Perchloric Acid Fume Hood
- use of perchloric acid requires a specialized fume hood
- contact fhsso@mcmaster.ca if you have or use perchloric acid
- stainless steel liner
- coved corners
- washdown system for ducting
- removable baffles
Radioisotope Use
- radioisotope use requires a fume hood designed for this purpose
- approval from health physics
- fume hood is assigned to you
After using Fume Hood
- secure all containers of hazardous materials
- let the fume hood run for 5 minutes
- remove all hazardous materials and equipment
- clean all work surfaces with water
- fully close the fume hood sash
FHS Equipment Inventory Labels
- all fume hoods in MUMC should have a FHSSO inventory label affixed. If there is no label, please notify fhsso@mcmaster.ca
- site visit to evaluate fume hood and affix label
- send fhsso@mcmaster.ca notification emails
- when unit has been removed
- when unit requires to be put out of service
- when unit has been inspected or certified
- when unit's contact person is updated
- when there is an issue with the unit
Maintenance and Annual Certification
- fume hoods are to be maintained by the users according to the manufacturer's instructions regardless of location
- malfunctioning fume hoods are to be reported and put out of service
- applying signage
- notifying lab occupants
- on campus buildings (MDCL, IAHS and CRL) are serviced by Facility Services
- off-site locations are responsible for servicing their own fume hoods through the building's engineering department or external service provider
- in all cases the fume hood is to be free of hazardous materials prior to servicing
Cleaning the Fume Hood
- use cleaning solutions compatible with the chemicals in use
- use cleaning solutions compatible with the surfaces of the fume hood
- follow manufacturer's instructions for cleaning fume hood
- clean the interior and exterior surfaces and sash periodically and after spills using deionized water; then wipe the areas down with a soap solution and rinse
- use a long handled tool to reach back and sides of the fume hood
- use a purpose tool for the sash i.e. the Glass Slider or the Glider
- https://www.youtube.com/watch?v=YzA7YFX3HQo
- https://www.youtube.com/watch?v=ey0j0G9wNP0
Emergency Exhaust
- your fume hood may have a controller and an option for emergency exhaust
- depending on your the HVAC system design, you may have constant air volume or variable air volume exhaust
- constant air volume systems do not have the ability to increase exhaust even if your fume hood has a control panel with an emergency exhaust button
- contact your building maintenance service to verify if your emergency exhaust switch on your fume hood is active
Downdraft Tables
- downdraft or necropsy tables are specially designed work areas with ventilation slots on the sides of the work area
- useful for work with human anatomical specimens and animal perfusions and other uses of chemicals with vapor densities heavier than air
- stainless steel table on wheels with slotted sides to capture toxic vapours and fumes from anatomical specimens
- also contains a sloped surface designed to collect fluids in a collection container beneath the table
- port for attaching exhaust source, detachable for movement of cadavers
- detailed equipment-specific training through the anatomy program
Elephant Trunks or Snorkels
- local exhaust ventilation
- not a substitute for a fume hood
- potential for contaminants to enter the user's breathing zone is high
- requirement for LEV to be registered with FHSSO and reviewed by JHSC
- SOPs to be generated by users and reviewed by JHSC
- tubing attached to the ventilation system to allow for highly localized exhaust
- exhaust area is very limited
- must be very close to hazard for effectiveness
- capture of contaminant is only effective within a distance of one duct diameter
- capture velocity required is dependent on the application i.e. passive capture or active capture
- flanged openings capture more contaminant than non-flanged openings
Fume Canopy
- constructed in a similar fashion to the overhead canopy hoods seen in kitchens
- in order for the canopy hood to be able to capture contaminants, the hood requires a relatively large volume of air movement, making them somewhat costly to operate
- the canopy hood works best when the thermal or buoyant forces exist to move the contaminant up to the hood capture zone
- they are designed such that the contaminated air passes through the user's breathing zone
- the airflow is easily disrupted by cross currents of air
- canopy hoods should only be used for exhaust of non-hazardous substances i.e. steam, odors from urine or fecal samples
- capture velocity required for effectiveness highly dependent on contaminant and process employed
- ACGIH Ventilation Manual
Other Ventilation Equipment
- slot ventilation table
- walk-in fume hoods
- glove boxes
Follow Up Expectations
- this awareness information to explain principles of equipment and basic function
- supervisor or competent person to demonstrate functioning of a fume hood, any special features and emergency procedures
- your supervisor shall ensure that you are to be chaperoned until the supervisor or competent person deems that you are proficient in fume hood use
- your supervisor shall provide you with equipment-specific, experiment-specific and lab-specific SOPs related to the fume hood
- if you are unsure about anything, ask your supervisor or contact the FHS Safety Office fhsso@mcmaster.ca
Updated 2021-11-09